ORDERING INFORMATION
Specify code number and variables.
-Code no.: SL-DSC-Input/Output-Power
(EX : SL-DSC-A1-Y)
-Specify special Output Range (Ex.0~5mA)
GENERAL SPECIFICATIONS
-Housing Material : Plastic ABS(Resin) Black
-Isolation : Input to Output to Power
-Easy Calibration of the Gain (Max.±40%of F.S) and Offset (Max.±20%of F.S).
-Triple Isolation for using on input & output of the PLC.
INSTALLATION
-Power Supply : DC 18~30V (Max.Current : 100 mA)-Reverse Polarity protected
-Operating Temperature : 0 ~ 40℃(Strong : -20 ~ 70℃)
-Operating Humidity : 90% RH max.(Non-condensing)
-Mounting : Rail mounting
-Dimension : 22.5(W)×75(H)×107(D) (Unit:mm)
-Weight : about 120g
PERFORMANCE
-Accuracy : ±0.2%of Full Scale
-Temperature Coefficient : ±0.015%/℃
-Response Time : 0.1Sec or less(0~90%),Normal
-Insulation Resistance : 100MΩ or more with 500V DC between Input/Output/Power
-Dielectric Strength : 1500V AC 0.5mA/Min (Input to Output to Power)
MODEL & SUFFIX CODE
Input Type & Range Selection
A : DC 4~20 mA (Impedance : 100 Ω)
B : DC 0~20 mA (Impedance : 100 Ω)
C : DC 1~5V (Impedance : 1 MΩ or more)
D : DC 0~5V (Impedance : 1 MΩ or more)
R : Other Special Spec.
Output Type & Range Selection (Precision : 750 Ω or less)
1 : DC 0~5V 2 : DC 1~5V
3 : DC 0~20mA 4 : DC 4~20mA
R : Other Special Spec.
Power Supply
X : AC 85 ~ 265V
Y : DC 18~30V